Página principal > Artículos > The half-sine method: a new accurate location method based on wavelet transform for transmission-line protection from single-ended measurements
Resumen: In this work, a new and accurate method based on the wavelet transform is proposed for fault location in transmission-line systems. The proposed wavelet method consists of the analysis of the transient signal measured at a single end of the transmission line. Aerial current modes are used, and zero modes are included in the fault-detection scheme for low fault-inception angles. The fault distance is evaluated using the wavelet modulus maxima technique and a method based on the response to a half-sine voltage is proposed to overcome drawbacks arising from the limited sampling frequency and low fault-inception angle. The fault distance is calculated using the difference between the time when a 100 kHz half-sine signal is sent and the time when the derivative signal is received. The proposed algorithm is tested considering harmonic distortion and varying fault resistance, ground resistivity, location and inception angle. The high accuracy of the proposed algorithm is obtained even for faults close to the bus and low inception angles Idioma: Inglés DOI: 10.3390/en12173293 Año: 2019 Publicado en: Energies 12, 17 (2019), 12173293 [15 p] ISSN: 1996-1073 Factor impacto JCR: 2.702 (2019) Categ. JCR: ENERGY & FUELS rank: 63 / 112 = 0.562 (2019) - Q3 - T2 Factor impacto SCIMAGO: 0.635 - Control and Optimization (Q2) - Electrical and Electronic Engineering (Q2) - Renewable Energy, Sustainability and the Environment (Q2) - Energy Engineering and Power Technology (Q2) - Fuel Technology (Q2) - Energy (miscellaneous) (Q2)