An anti-islanding protection based on RoCoF compliant with ENTSO-E and IEC 62116

Cañete López, D. (Universidad de Zaragoza) ; Martín-Arroyo, S. (Universidad de Zaragoza) ; García-Gracia, M. (Universidad de Zaragoza) ; Llamazares Prieto, A. (Universidad de Zaragoza) ; Sáez Martínez, I. (Universidad de Zaragoza)
An anti-islanding protection based on RoCoF compliant with ENTSO-E and IEC 62116
Financiación H2020 / H2020 Funds
Resumen: In case of unintentional islanding, distributed generation units must be able to detect it and disconnect from the grid in less than 2 seconds. In this work, a Rate of Change of Frequency (RoCoF) method has been developed for islanding detection. Since these algorithms are conditioned by the requirements of grid codes, ENTSO-E network code and IEC 62116 have been taken into account. The RoCoF anti-islanding algorithm has been developed in MATLAB-Simulink and implemented through rapid prototyping techniques in an FPGA ALTERA Cyclone V. To check the proposed protection algorithm, simulation tests have been carried out. Finally, the RoCoF anti-islanding protection has been validated using FPGA in the loop and experimentally in a real 20-kW inverter. © 2022, European Association for the Development of Renewable Energy, Environment and Power Quality (EA4EPQ). All rights reserved.
Idioma: Inglés
DOI: 10.24084/repqj20.307
Año: 2022
Publicado en: Renewable Energy and Power Quality Journal 20 (2022), 348-352
ISSN: 2172-038X

Factor impacto CITESCORE: 0.6 - Energy (Q4) - Engineering (Q4)

Factor impacto SCIMAGO: 0.148 - Electrical and Electronic Engineering (Q4) - Renewable Energy, Sustainability and the Environment (Q4) - Energy Engineering and Power Technology (Q4)

Financiación: info:eu-repo/grantAgreement/EC/H2020/783158/EU/first and euRopEAn siC eigTh Inches pilOt liNe/REACTION
Tipo y forma: Article (Published version)
Área (Departamento): Área Ingeniería Eléctrica (Dpto. Ingeniería Eléctrica)

Creative Commons You must give appropriate credit, provide a link to the license, and indicate if changes were made. You may do so in any reasonable manner, but not in any way that suggests the licensor endorses you or your use.


Exportado de SIDERAL (2023-09-13-12:53:01)


Visitas y descargas

Este artículo se encuentra en las siguientes colecciones:
Articles



 Record created 2022-10-06, last modified 2023-09-14


Versión publicada: